WAGO-I/O-SYSTEM 750
Parameterizing
75
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
Parameters
Description
Parameter
Address
Register
Brake-Mode
Selection of Brake mode
14
49
Stop-Mode_Entry
Transition to Stop mode
Increase_Swing_Back
Extending a swing-back drive
15
50
Extended_Infos
Reflection of information given in the
expanded status bytes S2 and S3
16
51
Swing_Back_Distance Display of current swing-back distance
17
52
The following tables show the assignment and factory setting of the individual
parameters.
8.6.1
RampTime_START, RampTime_STOP
Table 39: 2.2.1 RampTime_START, RampTime_STOP
Parameter address Function
Access Factory default
setting
0
RampTime_START,
0
Bit 0 ... 7: Duration of the start ramp [0 ... 255]
This value defines the duration of the start ramp to limit the current or "jerky" movements during
the start-up phase. The standard start behavior is defined with the start ramp length, which enables
start-up of the motor with or without softstart. For a soft start, the implemented ramp function is
used, taking the configured ramp duration into account. The ramp is executed when the configured
value is not equal to 0. The format of the parameter is an 8-bit wide unsigned integer in the value
range of 0 to 255.
0:
No ramp
1 ... 255:
Ramp duration 25 ms ... 6375 ms with a resolution of 25 ms
64:*
Default ramp duration 1600 ms
Bit 8 ... 15: Duration of the stop ramp [0 ... 255]
This value defines the duration of the stop ramp to limit the current or "jerky" movements during
the braking phase. The parameterized ramp duration also determines the behavior of the exception
stop. The ramp is executed when the configured value is not equal to 0. The parameter format
corresponds to an 8 bit wide integer value without sign, in the value range between 0 and 255.
0:
No ramp
1 ... 255:
Ramp duration 25 ms ... 6375 ms with a resolution of 25 ms
64:*
Default ramp duration 1600 ms
* Default settings