76
Parameterizing
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.6.2
Prestop_Pos
Table 40: 2.2.2 Prestop_Pos
Parameter address Function
Access Factory default
setting
1
Prestop_Pos
R/W
0x0064
Prestop value positive direction [0 ... 65535]
The configured value determines the prestop value to be used for optimization during a positioning
operation in a positive direction if the option is enabled in the control byte of the process image.
The value format corresponds to an 16 bit wide integer value without sign, in the value range
between 0 and 65535.
1 ... 65535:
Prestop value during positioning operations
100:*
Default prestop value positive direction
* Default settings
8.6.3
Prestop_Neg
Table 41: 2.2.3 Prestop_Neg
Parameter address Function
Access Factory default
setting
2
Prestop_Neg
R/W
0x0064
Prestop value negative direction [0 ... 65535]
The configured value determines the prestop value to be used for optimization during a positioning
operation in a negative direction if the option is enabled in the control byte of the process image.
The value format corresponds to an 16 bit wide integer value without sign, in the value range
between 0 and 65535.
1 ... 65535:
Prestop value during positioning operations
100:*
Default prestop value positive direction
* Default settings
8.6.4
Target_Window
Table 42: 2.2.3 Target_Window
Parameter address Function
Access Factory default
setting
3
Target_Window
R/W
0 x 000 A
Tolerance range [0 ... 65535]
The configured value determines the size of the tolerance window at the positioning motion. It
defines the window with +/- to the setpoint position.
The value format corresponds to an 16 bit wide integer value without sign, in the value range
between 0 and 65535.
0:
Positioning must stop when setpoint position = actual position.
1 ... 65535:
Positioning can stop on the window limits or within the window.
100:*
Default tolerance range
* Default settings