Parameterizing
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
Parameter address Function
Access Factory default
setting
Bit 8 ... 15: DirectionReversal_Delay [0 ... 255]
The motor interface delays the power-up procedure for n times 10 ms in case of rotation direction
reversal.
0:
No delay in case of rotation direction reversal
1 ... 255:
Delay 10 ms to 2550 ms with a resolution of 10 ms
10:*
Default delay 100 ms
* Default settings
8.6.9
Filter_Time
Table 47: 2.2.3 Filter_Time
Parameter address Function
Access Factory default
setting
9
Filter_Time
R/W
0x0AAA
Filter_Time
Debouncing times of the digital inputs with n times 3 ms.
Bit 0 ... 3: Debouncing time digital input E+ [0 ... 15]
0:
No software debouncing
1 ... 15:
3 ms to 45 ms debouncing time with a resolution of 3 ms
10:*
Default debouncing time 30 ms
Bit 4 ... 7: Debouncing time digital input E- [0 ... 15]
0:
No software debouncing
1 ... 15:
3 ms to 45 ms debouncing time with a resolution of 3 ms
10:*
Default debouncing time 30 ms
Bit 8 ... 11: Debouncing time digital input P [0 ... 15]
0:
No software debouncing
1 ... 15:
3 ms to 45 ms debouncing time with a resolution of 3 ms
10:*
Default debouncing time 30 ms
Bit 12 ... 13: Debounce time diagnosis signal for final stage (overload) [0 … 3]
Extremely short pulses (shorter than the filter period) are counted. The diagnosis signal is also
issued if more than 3 pulses occur within one minute.
0:*
0 ms (no filtering)
1:
0.5 ms
2:
1 ms
3:
3 ms
Bit 14 ... 15: Reserved
* Default settings