84
Parameterizing
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.6.13 Brake-Mode, Stop-Mode_Entry, Encoder_Limit_Frequency
Table 51: 2.2.3 Brake-Mode, Stop-Mode_Entry, Encoder_Limit_Frequency
Parameter address Function
Access Factory default
setting
14
Brake-Mode
Stop-Mode_Entry,
Encoder_Limit_Frequency
R/W
0x0105
Bit 0 ... 5: Brake-Mode
The brake mode determines the brake properties for the motor control. The brake mode distinguishes
between Idle, PWM ramp and Brake. The configured action is executed when the turn-off position is
reached and ends in the Stop mode.
Bit 0 ... 1: Brake-Mode_STANDARD [0 ... 3]
0:
Motor final stage sets motor at idle
1:*
Motor final stage sets PWM ramp
2:
Reserved
3:
Motor final stage decelerates
Bit 2 ... 3: Brake-Mode_EXCEPTION [0 ... 3]
0:
Motor final stage sets motor at idle
1:*
Motor final stage sets PWM ramp
2:
Reserved
3:
Motor final stage decelerates
Bit 4 … 5: Brake-Mode_EMERGENCY [0 ... 3]
0:*
Motor final stage sets motor at idle
1:
Motor final stage sets PWM ramp
2:
Reserved
3:
Motor final stage decelerates
Bit 6 ... 7: Reserved
Bit 8: Stop-Mode_Entry
This setting defines whether entry to the Stop mode is to take place unconditionally after reaching
the end of the electrical ramp, or via the Standstill condition.
0:
Without standstill condition
1:*
With standstill condition
Bit 9 ... 11: Limit frequency of the encoder pulses
Depending on the cable used, longer cable lengths can lead to A/B signal crosstalk with miscounting.
Decreasing this parameter size down to the maximum actual frequency of the encoder of the
respective application increases the filter function for this type of interference pulse. The scanning
frequency of the encoder signal is reduced internally, thus making the A/B inputs less susceptible to
interference pulses.
0:*
Limit frequency 500 kHz (scanning frequency 2 MHz)
1:
Limit frequency 125 kHz (scanning frequency 500 kHz)
2:
Limit frequency 62.5 kHz (scanning frequency 250 kHz)
3:
Limit frequency 25 kHz (scanning frequency 100 kHz)
4:
Limit frequency 12.5 kHz (scanning frequency 50 kHz)
5:
Limit frequency 6.25 kHz (scanning frequency 25 kHz)
6:
Limit frequency 2.5 kHz (scanning frequency 10 kHz)
7:
Limit frequency 1.25 kHz (scanning frequency 5 kHz)
Bit 12 ... 15: reserved
* Default settings