Parameterizing
WAGO-I/O-SYSTEM 750
750-636/000-x00 DC Drive Controller 24V/5A
Manual
Version 2.1.0
8.6.15
Extended_Infos
Table 53: 2.2.3 Extended_Infos
Parameter address Function
Access Factory default
setting
16
Extended_Infos
R
0x000
Bit 0 ... 8: Reflection of information given in the expanded status bytes S2 and S3. Information about
the individual bits is available in the chapter "Process Image" > "Extended Status Bytes".
Bit 0: Overtemperature_Warning
0:
The temperature is below the warning threshold.
1:
The temperature has exceeded the warning threshold.
Bit 1: Overtemperature
0:
The temperature is below the turn-off threshold.
1:
The temperature has exceeded the turn-off threshold.
Bit 2: Overflow_Warning
0:
The actual position is within the limit values.
1:
The actual position is outside the limit values.
Bit 3: 24 V_OK (depending on the I/O module used)
0:
The 24 V field power supply has failed. (only for 750-636)
A 24 V power supply system has failed. (only for 750-636/000-700)
1:
The 24 V field power supply is available. (only for 750-636)
Both 24 V power supply systems are available. (only for 750-636/000-700)
Bit 4: Overload
0:*
No overload error.
1:
Overload error.
Bit 5: MotionDetectionTimeout
0:
Pulses were received within the configured time period.
1:
No pulses were received within the configured time period.
Bit 6: Param_Write_Failed
0:
Parameterization successfully completed.
1:
Wrong parameters.
Bit 7: 24 V_Motor_OK (only 750-636/000-700)
0:
The 24 V motor supply voltage has failed.
1:
The 24 V motor supply voltage is available.
Bit 8: 24 V_Feld_OK (only 750-636/000-700)
0:
The 24 V field power supply has failed.
1:
The 24 V field power supply is available.
Bit 9 ... 15: Reserved