Reducing the heat-up time
During the transition from operation
with reduced room temperature to
operation with standard room tem-
perature, the boiler water or flow tem-
perature will be raised in accordance
with the selected heating curve. The
boiler water or flow temperature can
be automatically increased.
The value and duration of the addi-
tional increase of the set boiler water
temperature or flow temperature can
be adjusted in the coding addresses
"FA" and "Fb".
Example for the settings in the delivered condition
A
Start with standard room tempera-
ture
B
Set boiler water or flow tempera-
ture in accordance with the
selected heating curve
C
Set boiler water or flow tempera-
ture in accordance with coding
address "FA":
50 °C + 20% = 60°C
D
Duration of operation with raised
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min
Control functions
(cont.)
96
Function description
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...