External operating mode changeover
The "External operating mode chan-
geover" function is connected via
external extension input
aVD
. Coding
address "91" enables the selection,
which heating circuits the operating
mode changeover should affect:
Coding
The op. mode changeover affects:
91:0
No changeover
91:1
Heating circuit without mixer A1
91:2
Heating circuit with mixer M2
91:3
Heating circuit without mixer and heating
circuit with mixer
With coding address "D5", you can
select in which direction the change-
over should be made for each heating
circuit:
Coding
The op. mode changeover affects:
d5:0
Changeover in the direction of "Constantly
reduced" or "Constantly standby" mode
(respectively in accordance with the se-
lected set value)
d5:1
Changeover towards "Constantly heating
mode"
The duration of the operating mode
changeover can be adjusted in coding
address "F2".
Coding
The op. mode changeover affects:
F2:0
No operating mode changeover
F2:1 to
F2:12
Duration of the operating mode change-
over 1 to 12 hours
The operating mode changeover
remains active for as long as the con-
tact remains closed, however at least
as long as the duration selected in
coding address "F2".
Control functions
91
Function description
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...