Coding in the delivered condition
Possible change
A9:7
With pump idle time:
Heating circuit pump
OFF in case the set
value is changed (by
changing the operating
mode or the set room
temperature)
A9:0
Without pump idle time
A9:1
to
A9:15
With pump idle time, ad-
justable from 1 to 15
b0:0
With remote control:
Heating mode/reduced
mode: weather-com-
pensated
*
1
b0:1
Heating mode: weather-
compensated
Reduced mode: with
room temperature hook-
up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tem-
perature hook-up
b2:8
With remote control unit
and for the heating cir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influence factor
8
*
1
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
With remote control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
*
1
b5:1
to
b5:8
Heating circuit pump
logic function; see the fol-
lowing table
Parameter ad-
dress b5:...
With heating circuit pump logic function: Heating cir-
cuit pump OFF, if
1:
enabled RT
actual
> RT
set
+ 5 K; disabled RT
actual
< RT
set
+ 4 K
2:
enabled RT
actual
> RT
set
+ 4 K; disabled RT
actual
< RT
set
+ 3 K
Code 2
(cont.)
55
Coding
5692
536
GB
*1
Change the code for the heating circuit without mixer A1 or for the heating circuit with
mixer M2 only, if the remote control unit affects that heating circuit.
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...