Coding in the delivered condition
Possible change
Mixer circuit
F1:0
Screed function inactive F1:1
to
F1:5
Screed drying function
adjustable in accordance
with five optional tem-
perature/time profiles
(see page 93)
Note
Observe the screed sup-
plier's instructions.
Observe DIN 4725
–
2.
The report to be provided
by the heating contractor
must contain the follow-
ing heat-up details:
&
Heat-up data with
respective flow tem-
peratures
&
Max. flow temperature
achieved
&
Operating condition
and outside tempera-
ture during handover.
The function continues
after power failure or
after the control unit has
been switched OFF. The
heating program "
rw
"
will be started, after the
screed function has been
completed or if the ad-
dress is manually set to
0.
F1:6
to
F1:15
Constant flow tempera-
ture 20 °C
Code 2
(cont.)
58
Coding
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...