Coding in the delivered condition
Possible change
FA:20
Raising the set flow
temperature for the
transition from reduced
temperature to standard
room temperature mode
= 20%, see the example
on page 96
FA:0
to
FA:50
Raising the set flow tem-
perature for the transition
from reduced room tem-
perature mode to stan-
dard room temperature
mode, adjustable from 0
to 50%
Fb:30
Duration for raising the
set flow temperature
(see coding address
FA): 60 min, see the ex-
ample on page 96
Fb:0
to
Fb:150
Duration for raising the
set flow temperature ad-
justable from 0 to 150
(corresponds to 0 to 300
min)
Resetting codes to the delivered condition
1.
Press
L
and
G
simultaneously
for approx. 2 s.
2.
Press
e
.
"Confirm Standard setting? Yes"
with
d
.
With
a
or
b
, "Standard setting?
Yes" or "Standard setting? No" can
be selected.
Code 2
(cont.)
60
Coding
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...