Coding in the delivered condition
Possible change
E5:0
Without variable speed
circulation pump
E5:1
With variable speed cir-
culation pump; automatic
recognition
E6:65
Max. speed of the vari-
able speed pump 65%
of max. speed in stan-
dard mode
E6:0
to
E6:100
Maximum speed adjusta-
ble from 0 to 100% of
max. speed
E7:30
Min. speed of the vari-
able speed pump 30%
of max. speed
E7:0
to
E7:100
Min. speed adjustable
from 0 to 100% of max.
speed
E8:1
Min. speed subject to
the setting in coding ad-
dress "E9"
E8:0
Speed subject to the set-
ting in coding address
"E7"
E9:45
Speed of the variable
speed pump 45% of
max. speed in reduced
mode
E9:0
to
E9:100
Speed adjustable from 0
to 100% of max. speed
Code 2
(cont.)
57
Coding
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...