Coding in the delivered condition
Possible change
A5:5
With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump OFF, if
the outside temperature
(AT) is 1 K higher than
the set room tempera-
ture (RT
set
)
AT > RT
set
+ 1 K
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating
circuit pump OFF, if (see
the following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump OFF, if
1
AT > RT
Set
+ 5 K
2
AT > RT
Set
+ 4 K
3
AT > RT
Set
+ 3 K
4
AT > RT
Set
+ 2 K
5
AT > RT
Set
+ 1 K
6
AT > RT
Set
7
to
AT > RT
Set
- 1 K
15
AT > RT
Set
- 9 K
Code 2
(cont.)
53
Coding
5692
536
GB
Содержание Vitoplus 300
Страница 99: ...A1 Main PCB A2 Power supply unit Connection and wiring diagrams external connections 99 Designs 5692 536 GB ...
Страница 103: ...Parts lists cont 103 Parts lists 5692 536 GB ...
Страница 104: ...Parts lists cont 104 Parts lists 5692 536 GB ...
Страница 105: ...Parts lists cont 105 Parts lists 5692 536 GB ...
Страница 106: ...Parts lists cont 106 Parts lists 5692 536 GB ...
Страница 107: ...Parts lists cont 107 Parts lists 5692 536 GB ...
Страница 109: ...Service Service Service Service Commissioning service reports cont 109 Commissioning service reports 5692 536 GB ...
Страница 111: ...Service Service Service Service Commissioning service reports cont 111 Commissioning service reports 5692 536 GB ...
Страница 113: ...Service Service Service Service Commissioning service reports cont 113 Commissioning service reports 5692 536 GB ...
Страница 119: ...119 5692 536 GB ...