Checking the plate-type heat exchanger
Drain the boiler on its heating water
and DHW side.
During removal, small amounts of
water may trickle out and escape from
the removed plate-type heat exchan-
ger.
1.
Shut off and drain the boiler on its
heating water and DHW side.
2.
Release side closures and pivot
control unit forward (see page 11).
3.
Remove the siphon (see page 12).
4.
Release compression fittings
A
,
screws
B
and pull out plate-type
heat exchanger
C
.
5.
Check the connections on the heat-
ing water and DHW side for con-
tamination and scaling; if required,
replace the plate-type heat exchan-
ger.
6.
Lubricate the new gaskets/seals.
Install in reverse order with new
gaskets.
Checking the temperature limiter
If the burner control unit cannot be reset after a fault shutdown, although the
boiler water temperature is below approx. 75 °C, check the following:
Repairs
(cont.)
93
Troubleshooting
56
92
682
GB
Содержание Vitodens 333-F
Страница 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Страница 119: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 119 Designs 5692 682 GB ...
Страница 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Страница 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Страница 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Страница 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Страница 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Страница 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Страница 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...