Weather-compensated control
unit:
K
+
d
press simultaneously:
"Relay test"
and then
"Base load"
is shown.
4.
Check the CO
2
content. Should the
actual value deviate from the
above ranges by more than 1%,
implement steps from page 31.
5.
Enter actual values into the service
report.
6.
Adjust the upper output.
Constant temperature control
unit:
a
press:
"2"
is shown.
Weather-compensated control
unit:
a
press:
"Full load"
is shown.
7.
Check the CO
2
content. Should the
actual value deviate from the
above ranges by more than 1%,
implement steps from page 31.
8.
After testing, press
d
.
9.
Enter actual values into the service
report.
Matching the control unit to the heating system
Note
Subject to the equipment level, the control unit must be matched to the system.
Various system components are recognised automatically by the control unit
and the relevant codes are adjusted automatically.
&
For the selection of an appropriate design, see the following diagrams.
&
For coding steps, see page 46.
Further details regarding the individual steps
(cont.)
32
Commissioning, inspection, maintenance
56
92
682
GB
Содержание Vitodens 333-F
Страница 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Страница 119: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 119 Designs 5692 682 GB ...
Страница 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Страница 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Страница 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Страница 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Страница 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Страница 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Страница 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...