Coding in the delivered condition
Possible change
Level A1/M2
d4:0
Heating curve level = 0
(only for weather-com-
pensated control units)
d4:
–
13
to
d4:40
Heating curve level ad-
justable from
–
13 to 40
(see page 38)
Code 2
Calling up code 2
Note
&
On weather-compensated control
units, codes are displayed as plain
text.
&
Codes that are irrelevant due to the
system equipment level or the set-
ting of other codes will not be dis-
played.
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
d
to confirm.
3.
a
/
b
for the required coding
address; the address
flashes.
4.
d
to confirm; the value
flashes.
5.
a
/
b
for the selected value.
6.
d
to confirm; the display
briefly shows
"
accepted
" (for
weather-compensated
control units); the
address flashes again.
7.
a
/
b
for the selection of
further addresses.
8.
L
+
G
press simultaneously for
approx. 1 s; code 2 is
terminated.
The coding addresses are grouped
according to the following
function
areas
. The respective function area is
shown on the display.
The areas are scanned in the follow-
ing sequence with
a
/
b
:
Function area
Coding ad-
dresses
System design
00
Boiler/burner
06 to 54
DHW
56 to 73
General
76 to 9F
Heating circuit A1
(heating circuit
without mixer)
A0 to Fb
Heating circuit with
mixer M2
A0 to Fb
Code 1
(cont.)
48
Coding
56
92
682
GB
Содержание Vitodens 333-F
Страница 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Страница 119: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 119 Designs 5692 682 GB ...
Страница 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Страница 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Страница 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Страница 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Страница 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Страница 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Страница 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...