Fault
code
on the
display
Const.
weath.-
comp.
System char-
acteristics
Cause
Measures
F2
X
X
Burner in a
fault state
The tem-
perature lim-
iter has
responded.
Check the heating
system fill level.
Check the circula-
tion pump. Vent
the system.
Check the tem-
perature limiter
and connecting
cables.
Press "
E
RESET".
F3
X
X
Burner in a
fault state
Flame signal
is already
present at
burner start.
Check the ionisa-
tion electrode and
connecting cable.
Press "
E
RESET".
F4
X
X
Burner in a
fault state
No flame sig-
nal.
Check the ionisa-
tion electrode and
cable, measure
the ionisation cur-
rent, check the
gas pressure,
check the gas
train, ignition,
ignition module,
ignition electro-
des and the con-
densate drain.
Press "
E
RESET".
F7
X
X
Burner
blocked
Short circuit
or water
pressure
sensor lead
broken
Check the water
pressure sensor
and the intercon-
necting cable.
Fault codes
(cont.)
85
Troubleshooting
56
92
682
GB
Содержание Vitodens 333-F
Страница 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Страница 119: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 119 Designs 5692 682 GB ...
Страница 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Страница 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Страница 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Страница 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Страница 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Страница 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Страница 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...