Removing the burner and checking the burner gasket
(replace gasket every 2 years)
1.
Switch OFF the main power supply
and the ON/OFF switch at the con-
trol unit.
2.
Close the gas shut-off valve and
safeguard against reopening.
3.
Pull electrical cables from fan
motor
A
, gas valve
B
, ionisation
electrode
C
, ignition unit
D
and
earth tab
E
.
4.
Undo gas supply pipe fitting
F
.
Further details regarding the individual steps
(cont.)
21
Commissioning, inspection, maintenance
56
92
682
GB