1.
&
Boiler water temperature sen-
sor
Pull the leads from boiler water
temperature sensor
A
and
check the resistance.
&
Cylinder temperature sensor
Pull plug
%
from the cable har-
ness at the control unit and check
the resistance.
&
Flow temperature sensor
Pull plug "X3" from the control
unit and check the resistance
across terminals "X3.4" and
"X3.5".
2.
Check the sensor resistance and
compare the actual values with the
curve.
3.
Replace the sensor in case of
severe deviation.
Danger
The boiler water tempera-
ture sensor is immersed in
the heating water (risk of
scalding).
Drain the boiler before repla-
cing the sensor.
Repairs
(cont.)
90
Troubleshooting
56
92
682
GB