Gas type conversion (only for operation with LPG)
1.
Set adjusting screw
A
at the gas
train to "2".
2.
Switch ON/OFF switch "
8
" ON.
3.
Adjust the gas type in coding
address "82" (for a detailed
description of the individual steps,
see page 97):
&
Call up code 2
&
In coding address "11", select
value "9"
&
In coding address "82", select
value "1" (operation with LPG)
&
In code "11" select value
≠
"9".
&
Terminate code 2.
4.
Open the gas shut-off valve.
5.
Affix label "G31" (included with the
technical documentation) above
label "G20/G25" on the cover.
Function sequence and possible faults
Display screen
Measures
Control unit is-
sues heat de-
mand
No
Increase set
value and ensure
heat is drawn off
Yes
Fan starts
No
after approx. 51 s
fault F9
Check the fan, fan
connecting
cables, power at
the fan and fan
control
Further details regarding the individual steps
(cont.)
15
Commissioning, inspection, maintenance
56
92
682
GB
Содержание Vitodens 333-F
Страница 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Страница 119: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 119 Designs 5692 682 GB ...
Страница 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Страница 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Страница 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Страница 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Страница 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Страница 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Страница 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...