9
Cable lengths in the internal/external unit plus wall clearance
Cables
Internal unit
External unit
Power cables:
■ Heat pump control unit (230 V~)
2.0 m
–
■ Compressor (230 V~/400 V~)
–
1.5 m
Other connecting cables:
■ 230 V~, e.g. for circulation pumps
2.0 m
–
■ < 42 V, e.g. for sensors
2.0 m
–
Internal/external unit connecting cable:
■ 12 V BUS
2.5 m
1.5 m
■ 43 V BUS
2.5 m
1.5 m
Recommended power cables
Type AWT-AC
241.A04 to A13, B10, B13
Heat pump control unit
(internal unit) 230 V~
Cable cross-section
■ Without power-OFF
3 x 1.5 mm
2
■ With power-OFF
5 x 1.5 mm
2
Instantaneous heating water heater
Cable cross-section
■ 400 V~
5 x 2.5 mm
2
■ 230 V~
7 x 2.5 mm
2
Max. cable length
25 m
Type AWT-AC
241.A04
241.A07
241.A10
241.A13
External unit 230 V~
(compres-
sor)
Cable cross-section
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 4.0 mm
2
Max. cable length
29 m
25 m
20 m
20 m
or
or
Cable cross-section
–
– 3 x 4.0 mm
2
3 x 6.0 mm
2
Max. cable length
–
–
32 m
30 m
Type AWT-AC
241.B10
241.B13
External unit 400 V~
(compressor)
Cable cross-section
5 x 2.5 mm
2
5 x 2.5 mm
2
Max. cable length
30 m
30 m
Preparing for installation
Requirements regarding on-site connections
(cont.)
5546 699 GB
Installation
Содержание AWT-AC 241.A04
Страница 19: ...19 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 20: ...20 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5546 699 GB...
Страница 21: ...21 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5546 699 GB Service...
Страница 104: ...104 0010 0009 0007 0002 0004 0008 0001 0005 0003 0006 Parts lists internal unit Casing internal unit cont 5546 699 GB...
Страница 165: ...165 5546 699 GB...
Страница 166: ...166 5546 699 GB...
Страница 167: ...167 5546 699 GB...