83
Pump/component
Parameter
Setting
Vitocom 100, type GSM
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
"System definition"
Ó
"External extension
7010"
"1"
EA1
"2"
AM1
"3"
EA1 and AM1
Note
For parameters for external
functions, see the following
table.
External functions
External functions
Parameter
Setting
External demand
"Internal hydraulics"
, if ap-
plicable
Ó
"Flow temperature for ex-
ternal demand 730C"
Set flow temperature
for external demand
External starting of the com-
pressor; mixer in control
mode or OPEN
"System definition"
Ó
"Effect of external demand
on heat pump/heating cir-
cuits 7014"
"0"
to
"7"
(Observe parameter
"Flow temperature
for external demand
730C"
)
External changeover of the
operating status of various
system components
"System definition"
Ó
"System components for
external changeover
7011"
"0"
to
"127"
"System definition"
Ó
"Operating status for ex-
ternal changeover 7012"
"0"
to
"3"
"System definition"
Ó
"Duration of external
changeover 7013"
"0"
to
"12"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5546 699 GB
Service
Содержание AWT-AC 241.A04
Страница 19: ...19 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 20: ...20 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5546 699 GB...
Страница 21: ...21 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5546 699 GB Service...
Страница 104: ...104 0010 0009 0007 0002 0004 0008 0001 0005 0003 0006 Parts lists internal unit Casing internal unit cont 5546 699 GB...
Страница 165: ...165 5546 699 GB...
Страница 166: ...166 5546 699 GB...
Страница 167: ...167 5546 699 GB...