External unit power supply 230 V~/400 V~
■ Economy tariff and power-OFF can be
used.
■ No parameters need to be set when
using economy tariff with power-OFF.
The compressor is shut down during
the power-OFF period.
■ During power-OFF, the diagnostic
functions for the external unit are not
supported.
Note
Free terminals for internal use.
External unit power supply 230 V~
Type AWT-AC
241.A04
?
C N L
?
B
L1
N
A
241.A07
COM
Ni
?
Li
N
0
L
0
B
?
N L1
A
?
241.A10 and A13
?
N L
?
N L
C2 C1
B
?
N L1
A
A
Wiring chamber, external unit: See
page 52.
B
Power supply 230 V/50 Hz
Type AWT-AC
241.A04
241.A07
241.A10
241.A13
Recommended power
cable
3 x 2.5 mm
2
(max. 29 m)
3 x 2.5 mm
2
(max. 25 m)
3 x 2.5 mm
2
(max. 20 m)
3 x 4.0 mm
2
(max. 20 m)
or
3 x 4.0 mm
2
(max. 32 m)
3 x 6.0 mm
2
(max. 30 m)
Fuse protection
B20A
B20A
B20A
B32A
Installation sequence
Power supply
(cont.)
5546 699 GB
Содержание AWT-AC 241.A04
Страница 19: ...19 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 20: ...20 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5546 699 GB...
Страница 21: ...21 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5546 699 GB Service...
Страница 104: ...104 0010 0009 0007 0002 0004 0008 0001 0005 0003 0006 Parts lists internal unit Casing internal unit cont 5546 699 GB...
Страница 165: ...165 5546 699 GB...
Страница 166: ...166 5546 699 GB...
Страница 167: ...167 5546 699 GB...