141
Cooling
Parameter
Code
Delivered
condition
Commis-
sioning
Mainte-
nance/
Service
"Cooling function"
7100
0
"Cooling circuit"
7101
1
"Set room temperature sepa-
rate cooling circuit"
7102
200 (
≙
20 °C)
"Min. flow temperature cool-
ing"
7103
50 (
≙
5 °C)
"Influence room temperature
hook-up cooling circuit"
7104
0
"Ranking room temp sensor
separate cooling circuit"
7106
0
"Cooling curve level"
7110
0 (
≙
0 K)
"Cooling curve slope"
7111
12 (
≙
1.2)
"Remote control cooling circ"
7116
0
"Enable active cooling"
71FE
0
Ventilation
Parameter
Code
Delivered
condition
Commis-
sioning
Mainte-
nance/
Service
"Vitovent enable"
7D00
0
"Enable preheater bank elec-
tric"
7D01
0
"Enable reheater bank hy-
draulic"
7D02
0
"Enable humidity sensor"
7D05
0
"Enable CO2 sensor"
7D06
0
"Set extract air temperature"
7D08
200 (
≙
20 °C)
"Flow rate reduced ventila-
tion"
7D0A
120 m
3
/h
"Flow rate nominal ventila-
tion"
7D0B
170 m
3
/h
"Flow rate intensive ventila-
tion"
7D0C
215 m
3
/h
"Min. supply air temperature
for bypass"
7D0F
160 (
≙
16 °C)
"CO2 value for raising the flow
rate"
7D18
800 ppm
Commissioning/service reports
Control parameters report
(cont.)
5546 699 GB
Service
Содержание AWT-AC 241.A04
Страница 19: ...19 SLP N 9 11 aCH sG lJ 10 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 20: ...20 X20 2x 16 17 2x 12 14 18 13 15 Installation sequence Installing the internal unit cont 5546 699 GB...
Страница 21: ...21 2x 4x 4x 6x 21 19 20 22 Installation sequence Installing the internal unit cont 5546 699 GB Installation...
Страница 89: ...89 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5546 699 GB Service...
Страница 104: ...104 0010 0009 0007 0002 0004 0008 0001 0005 0003 0006 Parts lists internal unit Casing internal unit cont 5546 699 GB...
Страница 165: ...165 5546 699 GB...
Страница 166: ...166 5546 699 GB...
Страница 167: ...167 5546 699 GB...