74
1.
8x
B
A
2.
!
Please note
A short circuit between the mag-
nesium anode and internal indi-
rect coil increases the protective
effect of the magnesium anode
and leads to corrosion damage
on the DHW cylinder.
Before inserting the electrical
cables, measure the resistance
between terminals
A
and
B
. If
the resistance is significantly less
than infinity, check whether the
magnesium anode is touching
the internal indirect coil.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5546 699 GB