88
Operation
IM-HC 599871 0321 RABS
6.1.19 Central Settings / Limit Supply Temperature Menu
Figure 62: Limit supply temperature
The limitation of the supply temperature protects the system from
overheating while in heating mode, and from falling below dew point in
cooling mode.
X
Set the slide for the minimum and maximum supply temperature to
the desired temperature.
6.1.20 Central Settings / Analyze Supply Temperature Menu
Figure 63: Analyze supply temperature
Indication of the mean value of the supply temperatures of the last
20 operating days as a major indicator for the energetic state of the
system.