Hardware Set-Up Procedures
To log the range extender in, the following conditions must be met:
The range extender must be approximately 3.3 feet away from the
control unit.
The range extender must be connected to the power supply.
Log-in process
X
Radio amplifier: Keep the “connect” and “ok” buttons pressed
simultaneously.
Z
The LEDs flash.
X
Radio amplifier: Release the “connect” and “ok” buttons.
Z
“– –” is indicated.
X
Control unit: Briefly press the “connect” button.
Z
The “connect” LED flashes.
X
Control unit: Briefly press the “connect” button.
Z
The “connect” LED emits light.
X
Radio amplifier: Briefly press the “connect” and “ok” buttons
simultaneously.
Z
“Con” is indicated briefly.
X
Control unit: Press the “ok” button.
Z
The LED “connect” goes out — the log-in process is completed.
Logging the Thermostat into the Range Extender
The following conditions must be met so that you can log the
thermostat in to the range extender:
The thermostat must be logged in to the control unit.
The range extender must be logged in to the control unit.
The thermostat must be approximately 3.3 feet away from the range
extender.
Log-In Process
X
Remove the batteries from the thermostat.
X
Keep the “+” / “-” buttons at the thermostat pressed and insert the
batteries.
X
Keep the “+” / “-” buttons pressed until both LEDS flash red.
X
Radio amplifier: Press the “connect” button.
Z
The LED flashes.
X
Radio amplifier: Press the “ok” button.
Z
The LED emits light.
X
Room thermostat: Press the “+” and “-” buttons simultaneously until
the “connect” LED goes out.
Z
The thermostat briefly indicates “– –”, followed by the current
room temperature.
Z
The thermostat is logged in.
Ä
4.4 “Checking the Wireless Connection to the Thermostat” on page 52.