26
••••
Wiring
XX100-00-01 Rev 202 Surveyor1000 Camera Dome System
Typical Relay and Alarm Connections
Alarm Input and Relay Output type signals are also carried on individually-shielded twisted-pair cable sets.
The signals are defined in the following descriptions.
Alarms 1-4 are electronic TTL (transistor-transistor
logic) type inputs that are driven by a dry contact
type switch. These signals are connected to RJ-45
Connector J2. Each input has two states, open and
closed. For example, in Figure 19, a door switch
can activate an alarm when connected to a
Surveyor1000 Alarm Input. As a guideline (under
normal conditions), the cable should be 22 AWG for
a 1000 foot (305 m) distance. The states
correspond to defined TTL designations as follows:
OPEN = HIGH and CLOSED = LOW
where: HIGH = 5 VDC and LOW = < 1 VDC
Since dry contact switches are normally defined in
terms of their inactive or “normal” state, the
following holds true:
NORMALLY CLOSED (NC) = ACTIVE HIGH
(OPEN)
NORMALLY OPEN (NO) = ACTIVE LOW
(CLOSED)
The “active” state can be programmed through the
Surveyor1000 menu system. These signals are
connected to RJ-45 Connector J3. Alarm signals
can be programmed for their status
(enabled/disabled), active level definition (high/low),
action/reset function (none, preset, aux on, aux off
or tour), acknowledgment mode (automatic/manual)
and report status (yes/no).
The Relay Output is an actual Relay Output dry
contact which directly drives external devices. For
example, a light can be turned on and off when the
Relay Output is connected to the light circuit. Refer
to Figure 20. The Relay Output contact can be
programmed for its power-on state definition (on/off)
and output type definition (momentary or latching).
The Relay Output can handle a signal of about 35
volts at 1 A typical. There is one Relay Output
contact located on the J3, RJ-45 Connector.
Connect the circuit to be switched to the connector
pins labeled RELAY C and RELAY NC or RELAY
NO for a normally closed or normally open
connection, respectively.
Figure 19
Typical Alarm Circuit
Figure 20
Typical Relay Circuit
Содержание surveyor 1000
Страница 2: ......
Страница 3: ......
Страница 4: ......
Страница 30: ...24 Installation XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 40: ...34 Wiring XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 44: ...38 Configuration XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 46: ...40 Uninstalling the Surveyor1000 XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 50: ...44 Operation XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 54: ...48 Shipping Instructions XX100 00 01 Rev 202 Surveyor1000 Camera Dome System NOTES ...
Страница 61: ...XX100 00 01 Rev 202 Surveyor1000 Camera Dome System Technical Information 55 Figure 37 Dimensions ...