38
Parameter
Description
Units
Set by the
manufacturer
Range
Resolution
P 56
Heating circuit pump off/on
-
0 … 1
1
P 57
Heating circuit pump slowing-down
[min.]
3
0 … 60
1
P 58
Day of heating circuit pump spinning
5
0 … 8
1
P 59
Warm water pump man/auto
1
0 … 1
1
P 60
Warm water pump off/on
-
0 … 1
1
P 61
Warm water pump slowing-down
[min.]
3
0 … 10
1
P 62
Day of warm water pump spinning
5
0 … 8
1
P 70
Outside temperature reset
0
0 … 1
1
P 71
Space hysteresis
[
o
C]
0,5
0,1 … 5
0,1
P 72
Space effect
[%]
20
0 … 100
1
P 76
Minimum heating circuit temperature
[
o
C]
30
20 … 50
1
P 77
Maximum heating circuit temperature
[
o
C]
80
30 … 90
1
P 80
Building constant
[h]
10
1 … 50
1
P 81
Temperature ECO
[
o
C]
-3
-5 … 5
1
P 82
ECO automatics passive/active
-
0 … 1
1
P 83
Temperature summer/winter
[
o
C]
17
8 … 35
1
P 84
Constant summer/winter
[h]
50
1 … 100
1
P 85
Current status summer/winter
-
0 … 1
1
P 86
Heating system
3
0 … 3
1
P 87
HC antifreeze protection off/on
1
0 … 1
1
P 88
Servo overruntime
[s]
120
10 … 1800
1
P 100
Setting the day of time schedule for HC
1
0 … 7
1
P 101
First HC period switched on
[h:min.]
6:00
0:00 … 23:59
1 min.
P 102
First HC period switched off
[h:min.]
22:00
0:00 … 23:59
1 min.
P 103
Desired space temperature in the first period
[
o
C]
21
10 … 30
0,1
P 104
Second period HC switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 105
Second period HC switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 106
Desired space temperature in the second period
[
o
C]
21
10 … 30
0,1
P 107
Third period HC switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 108
Third period HC switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 109
Desired space temperature in the third period
[
o
C]
20
10 … 30
0,1
P 110
Time schedule reset HC
0
0 … 1
1
P 111
Desired space temperature in attenuation
[
o
C]
19
5 … 25
0,1
P 120
Setting the day of time schedule for HW
1
0 … 7
1
P 121
First period HW switched on
[h:min.]
6:00
0:00 … 23:59
1 min.
P 122
First period HW switched off
[h:min.]
22:00
0:00 … 23:59
1 min.
P 123
Desired temperature HW in the first period
[
o
C]
60
10 … 65
1
P 124
Second period HW switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 125
Second period HW switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 126
Desired temperature HW in the second period
[
o
C]
55
10 … 65
1
P 127
Third period HW switched on
[h:min.]
23:59
0:00 … 23:59
1 min.
P 128
Third period HW switched off
[h:min.]
23:59
0:00 … 23:59
1 min.
P 129
Desired temperature HW in the third period
[
o
C]
50
10 … 65
1
P 131
HW Time schedule reset
0
0 … 1
1
P 140
Feeder runtime
[s]
5,5
3 … 10
0,1
P 150
Feeder X1 lignite
[%]
0
0
0
P 151
Feeder Y1 lignite (3 sect./4 sect.)
[s]
95/75
60..130/50..110
1
P 152
Feeder X2 lignite
[%]
33
33
0
P 153
Feeder Y2 lignite (3 sect./4 sect.)
[s]
58/40
35..90/25..110
1
P 154
Feeder X3 lignite
[%]
66
66
0
P 155
Feeder Y3 lignite (3 sect./4 sect.)
[s]
36/26
15..80/10..80
1
P 156
Feeder X4 lignite
[%]
100
100
0
P 157
Feeder Y4 lignite (3 sect./4 sect.)
[s]
25/18
15..80/10..80
1
P 158
Feeder runtime in the attenuation – lignite
[s]
10
3 … 20
1
P 159
Standstill time(delay) feeder in the attenuation –
lignite
[min]
40
10 … 240
1
P 160
Ventilator X1 lignite
[%]
0
0
0
P 161
Ventilator Y1 lignite (3 sect./4 sect.)
[%]
20/27
5..60/5..80
1
P 162
Ventilator X2 lignite
[%]
33
33
0
P 163
Ventilator Y2 lignite (3 sect./4 sect.)
[%]
25/34
5..80/5..90
1
P 164
Ventilator X3 lignite
[%]
66
66
0
P 165
Ventilator Y3 lignite (3 sect./4 sect.)
[%]
33/41
5..90/5..90
1
P 166
Ventilator X4 lignite
[%]
100
100
0
P 167
Ventilator Y4 lignite (3 sect./4 sect.)
[%]
45/53
5..90/5..90
1
P 168
Ventilator slowing-down in the attenuation
regime– lignite
[s]
90
5 … 200
1