17
User Manual 10H52258UM60 - Rev. 3 - 01/2019
Mechanical Installation
APM 400/600
See Table 3.2 below the module address setting procedure:
Table 3.2
DIP switch setting
Module address
DIP switch setting
Module address
1
7
2
8
3
9
4
10
5
11
6
12
1.
Set the ready switch on the front panel of the module to the UP position (the UP position corresponds to the
unready state).
2.
Remove the dummy plate, and then insert the module into the installation position and push it into the cabinet.
3.
Secure the module to the cabinet via the mounting holes on either side of the front panel of the module.
4.
Set the ready switch to the Down position (the Down position corresponds to the ready state).
3.7
Installation Drawings
This section contains the installation drawings, which indicate the dimensions of the APM 400/600 MODULAR UPS.
For an overall picture of the dimensions, it is necessary to take into account the Top, Front, Side and Bottom views.
Figures 3-7 and 3-9 illustrate the different views and dimensions of the product.
Figures 3-8 and 3-10 show the bottom view of the APM 400/600 modular UPS, complete with Seismic anchors.