Mechanical Installation
APM 400/600
3
Mechanical Installation
The previous section deals with the environmental and ambient conditions necessary to obtain the maximum
performance from the UPS system. This section provides a detailed description of the UPS installation procedures.
Warning
Do not remove the package without the permission or approval of the authorized service engineer. Ensure that all
the instructions set out in this manual, and on the labels present on the unit are observed prior to installation.
The UPS system is suitable for connection to power systems where the neutral conductor is not connected to earth
(i.e. IT systems), and TN and TT AC 3 phase, 5 wire (A, B, C, N and PE) distribution systems (IEC60364-3).
Battery Hazard
Warning
Personnel must proceed with extreme care while installing the batteries or carrying out any other operation that
involves handling them. When connecting the batteries, the terminal voltage reaches 320Vdc, which can cause
severe injury, and may even be fatal to personnel if not handled properly.
The following is a list of safety measures that must be observed
while connecting or handling the batteries:
•
Wear safety glasses to protect the eyes from arcing.
•
Remove all metal and conductive items, such as rings and watches.
•
Use insulated tools and rubber gloves.
•
Replace any batteries that may be damaged or leak electrolyte. When decommissioning batteries, place them in
containers that are capable of withstanding sulfuric acid and dispose of them in accordance with locally applicable
regulations and protocols.
•
If the skin comes into contact with the electrolyte, clean and flush it using water immediately.
3.1
Unpacking
The UPS cabinet is heavy and, therefore, we recommend using an electric fork-lift when unloading and moving it to
the installation site. If an electric forklift is used, insert the tines of the forklift below the bottom pallet as shown in
Figure 3-1. This prevents the equipment from falling over.
Note
The center of gravity of the UPS cabinet is not centered by default. Therefore, use a fork-lift to prevent it tipping
over while it is being moved.