VSP-VP-6124-UPS 

 

 

Issue 3 

 

1

 

947271 

 

 
 
   

 

VP-6124-UPS 

 

ADD ON OPTION FOR THE VP-6124/VP-6124-E 

 

POWER SUPPLY

 

 
 

 

INTRODUCTION 

The VP-6124-UPS is an optional unit that allows the 
VP-6124/VP-6124-E to supply power during a power 
outage.  
 
The VP-6124-UPS is comprised of a VP-6124-UPS 
(Charger) and a VBB-1424 (Battery Enclosure).  The 
VP-6124-UPS connects to the VP-6124 Power Supply 
(To receive power to charge the batteries).   
 
Listed below are specifications and recommendations 
for power sources as well as precautionary 
instructions. 
 

UPS Float Standby Charging

 

Charging Voltage: 

27.6 Volts (13.8 Volts per battery) 

Current Limit: 

900mA charging 

 

100mA at 27 Volts final charge 

Fusing: 

1 Amp auto-reset polyswitch 

 

6 Amps accidental reverse battery polyswitch 

 

Time Required to Recharge Battery 

7AH Battery: 

14 hours 

 

Length of Time Battery Will Provide 
Power

 

• 

With four 7AH 12V batteries for 14AH total 

        

3 Amps load draw: 

3 hours run time 

        

6 Amps full load: 

1.5 hours run time 

Use of batteries greater than 7AH is not 
recommended since 90% of all power outages are less 
than an hour in length and the time to evacuate a 
building is less than an hour. 
 

NOTE:  To insure trouble-free UPS back-up 
operation, five years batteries must be replaced five 
years from the date of manufacturing. 
 

DIMENSIONS/WEIGHT 

• 

10.30

"

H x 3.50

"

W x 2.25

"

• 

(26.16cm H x 8.89cm W x 5.72cm D) 

 

2.90 lbs. (1.32 kg)

 

 

INSTALLATION 

The VP-6124-UPS (Charger) is designed for 

wall 

mounting only.  

Screw the mounting plate to the wall 

near the VP-6124/VP-6124-E and position the 
VP-6124-UPS onto the mounting plate. 
 
Attach the UPS unit securely to the bracket lip using 
the 6-32 x 3/8" long Phillips head self-tapping screw 
supplied.  Place the VBB-1424 on the floor within six 
feet of the unit.  
 

CONNECTIONS 

• 

Disconnect AC power from the power supply. 

• 

Remove plug button from the VP-6124/VP-6124-E. 

• 

Remove wire access cover from the 
VP-6124/VP-6124-E.  

• 

Using the cable designated by the tag labeled 
Valcom P/N WA-784 with four positions 
connector and attached to VP -6124-UPS 
(Charger), place the Molex connector through the 
hole on the power supply and connect the 
charger to the Molex input connector on the 
VP-6124 Power Supply. 

• 

Snap strain relief into place. 

• 

Replace wire access cover on the 
VP-6124/VP-6124-E. 

• 

Remove cover from Battery Backup. 

• 

Push cable labeled Valcom P/N WA-783 with two 
positions connector through the hole on the  
battery enclosure and snap strain relief into 
place. 