5
System Setup
Tank Periodic Test Needed Warnings
5-8
To enable Weekly Variance Analysis Reports, press CHANGE, ENTER, then STEP.
PERIODIC VARIANCE ANALYSIS REPORTS
If necessary, press STEP until you see the message:
To enable Periodic Variance Analysis Reports, press CHANGE, ENTER, then STEP.
Tank Periodic Test Needed Warnings
If necessary, press STEP until you see the message:
The system monitors the amount of time since the last passed 0.2 gph (0.76 lph) tank test. By enabling the Tank
Periodic Test Needed Warnings, you can have the system provide a warning when a tank test has not been
passed, or conducted in a specified number of days (0 to 30), and activate an alarm if a test has not been passed
after a warning, or a specified number of days.
ENABLE TANK PERIODIC TEST NEEDED WARNINGS AND ALARMS
To enable Tank Test Needed Periodic Warnings, press STEP. The system displays the message:
Press CHANGE, and enter the number of days (0 to 30 days) after which you want the system to warn that a tank
test has not been passed. Press ENTER. The system displays the message:
Press STEP. The system displays the message:
Press CHANGE, and enter the number of days (0 to 30) after which you want an alarm if a test has not been
passed. This number should be higher than the number you set for the periodic warning. Press ENTER. The
system displays the message:
Press STEP. (The system displays the Tank Annual Test Needed Warnings message.)
PERIODIC VAR ANALY RPTS
DISABLED
TANK PER TST NEEDED WRN
DISABLED
TANK PER TST NEEDED WRN
DAYS = XX
DAYS = XX
PRESS <STEP> TO CONTINUE
TANK PER TST NEEDED ALM
DAYS = XX
DAYS = XX
PRESS <STEP> TO CONTINUE