11-7
11
Wireless Pressurized Line Leak Detection
Setting Up Additional WPLLDs
•
MANIFOLDED: ALTERNATE
1
- The pump will run in the tank with the greatest inventory volume.
•
MANIFOLDED: SEQUENTIAL
1
- The tanks are pumped low one at a time. When the tank’s volume drops
below the entered Pump Threshold percentage, pumping will switch over immediately to the next available tank
in the line manifolded set. Pumping will continue from the current tank for another 10 seconds to avoid a
disruption in dispensing during the switch over. (see “Pump Threshold” on page 7-26).
•
MANIFOLDED: ALL PUMPS - All pumps on the line are run.
Press CHANGE until your choice appears then press ENTER to continue.
Setting Up Additional WPLLDs
If you have additional WPLLDs to set up, press STEP to return to the WPLLD LINE LABEL message:
Press TANK/SENSOR to access another WPLLD. Repeat the steps described above, beginning with “Labeling
WPLLDs” on page 11-2. After you have entered setup information for all WPLLDs in the system, press
FUNCTION to exit.
1. To prevent backfilling, the level of all tanks connected to the line will be monitored. If the level of any tank
exceeds 95% of the Max or Label Volume limit (see “Max or Label Vol” on page 7-16), the pump for that
tank will also be turned on during dispensing. The state of the pump that was already ON will not be
changed.
WPLLD LINE LABEL
W1: