26-3
26
Smart Sensor Setup
Mag Sensor Setup
•
Vapor Pressure
•
Mag Sensor
•
Vac Sensor
•
ATMP Sensor (NOTE: The atmospheric pressure [ATMP] sensor is resident in the Smart Sensor / Press
Module. One ATMP sensor is required with Vac Sensor systems per site. You only need to configure the ATMP
sensor, there is no setup [other than assigning a label]. A Setup Data Warning will be posted for all Vac Sensors
if an ATMP sensor is not present and configured)
•
Unknown
Mag Sensor Setup
If the Mag Sump Sensor you installed has
NO
programmable features (i.e., alarm upgrade delay, water warning
height, or water alarm height), you will not be able to enter Mag Sensor Setup after entering Smart Sensor label
and Sensor Category.
If necessary, press STEP until you see the message:
Press ENTER:
This display appears if the alarm upgrade delay has been factory set to programmable. This is the time in hours
that all uncleared warnings will delay before upgrading to alarms. Also, this upgrade only applies to Smart Sensor
warnings that have been factory set to upgrade.
If necessary, press CHANGE and enter the number of hours (up to 9999) to delay upgrades. Entering 0 disables
the Alarm Upgrade Delay feature. Press ENTER to confirm your entry.
Press STEP to continue.:
This display appears only if the Water Warning has been factory set to programmable. This is the height in inches
(or mm if metric units selected) at which the Water Warning will activate. Refer to your Smart Sensor setup
printout’s Min/Max Thresholds for the permissible range within which to select this value.
If necessary, press CHANGE and enter the Water Warning height. Press ENTER to confirm your entry.
Press STEP to continue.:
This display appears only if the Water Alarm has been factory set to programmable. This is the height in inches (or
mm if metric units selected) at which the Water Alarm will activate. Refer to your Smart Sensor Setup printout’s
Min/Max Thresholds for the permissible range within which to select this value.
If necessary, press CHANGE and enter the Water Alarm height. Press ENTER to confirm your entry.
s 1: MAG SENSOR SETUP
PRESS <ENTER>
s 1: (Name)
ALM UPGRADE DELAY: XXXX
s 1: WATER WARNING
WATER HT
>
0002.0
s 1: WATER ALARM
WATER HT
>
0005.0