17-3
17
Reconciliation Setup
Periodic Reconciliation Alarm
each month. If you choose ROLLING, a report will automatically be printed at the end of the interval you choose (1
- 31 days).
To accept MONTHLY, press STEP. (The system displays the PERIODIC RECONCILIATION ALARM message.)
To switch to ROLLING, press CHANGE and press ENTER. They system displays:
Press STEP. The system displays the following message:
Press CHANGE. Enter the number of days (1–31) between the printing of each periodic reconciliation report.
Then press ENTER. The system confirms your entry with the message:
Press STEP to continue.
Periodic Reconciliation Alarm
If necessary, press STEP until you see the message:
If enabled, the Periodic Reconciliation Alarm will be activated when the programmed threshold for discrepancies
between fuel delivery amount and dispensed fuel amount is exceeded. The system default is 1.00% of throughput
plus 130 gallons (492 litres) offset. In the U.S. the EPA has set this default as a criteria not to be exceeded. The
Periodic Reconciliation Alarm is triggered when the alarm threshold plus offset exceeds the allowed variance.
To leave the Periodic Reconciliation Alarm disabled, press STEP until you see the REMOTE REPORT FORMAT
message. (The system displays the PERIODIC RECONCILIATION ALARM THRESHOLD message.)
To enable the Periodic Reconciliation Alarm, press CHANGE, then press ENTER. The system confirms your entry
with the message:
Press STEP. The system displays the message:
Press CHANGE. Enter the percent of total meter sales (throughput).
Note - the Alarm Threshold must be
between 0.00 and 5.00 percent.
Press ENTER. The system confirms you entry with the message:
MODE: ROLLING
PRESS <STEP> TO CONTINUE
PERIODIC RECONCILIATION
LENGTH: XX DAYS
LENGTH: XX DAYS
PRESS <STEP> TO CONTINUE
PERIODIC RECONCILIATION
ALARM: DISABLED
ALARM: ENABLED
PRESS <STEP> TO CONTINUE
PERIODIC RECONCILIATION
ALARM THRESHOLD: 1.00
ALARM THRESHOLD: X.XX
PRESS <STEP> TO CONTINUE