24-3
24
Output Relay Setup
Assignment Method
If you select PUMP CONTROL OUTPUT or PUMP COMM CONTROL relay types, you will prompted to specify a
tank number.
Press ENTER to confirm your choice. The system displays:
Press STEP to display the message:
For Pump Control Output relay selection, press CHANGE and enter the tank number of the assigned Pump Sense
module or Line Leak module.
For Pump Comm Control relay selection, press CHANGE and enter the number of the tank in the manifolded set
which is assigned to the PLLD or WPLLD module.
In either case, press ENTER to confirm your entry. The system displays:
Press STEP to continue.
Assignment Method
This function allows you to assign alarms and external inputs for each relay (except Pump Comm Control relay). For
the selected relay, you will first specify whether you want to assign an available alarm type (e.g., In-Tank, Liquid
Sensor, etc.) or external input to that relay by choosing Yes or No for that type of alarm or input. For all alarms
except System, if you choose Yes, you must then specify the method of assignment (none, all, or single) for each
alarm condition.
NOTE
:
You may assign more than one in-tank alarm, sensor alarm, and external input to a relay, and you may assign
any in-tank alarm, sensor alarm, and external input to more than one relay.
As you step through possible relay assignments, the system automatically displays all in-tank alarms, sensor
alarms, line leak alarms and external inputs that have been configured in the system. If no other sensors or inputs
are configured, the system returns to the RELAY DESIGNATION message. Refer to the section entitled “Setting
Up Additional Relays” on page 24-8.)
IN-TANK ALARMS
If necessary, press STEP until you see the message:
If you do not want to assign In-Tank Alarms to the relay displayed in the first line of the IN- TANK ALARMS
message, press STEP. (The system displays the next available alarm or input assignment group.
To assign In-Tank Alarms to the selected relay, press CHANGE in response to the IN-TANK ALARMS: NO
message. Press ENTER to confirm your choice. The system displays:
PUMP CONTROL OUTPUT
PRESS <STEP> TO CONTINUE
PUMP COMM CONTROL
PRESS <STEP> TO CONTINUE
or
R1: SELECT TANK
NONE
TANK #: X
PRESS <STEP> TO CONTINUE
R1:(Name)
IN-TANK ALARMS: NO
IN-TANK ALARMS: YES
PRESS <STEP> TO CONTINUE