7-9
7
In-Tank Setup
Full Volume
50 POINT TANK PROFILE ENTRIES WITH TANK CHART SECURITY ENABLED
If you selected 50 points for Tank Profile AND Tank Chart Security has been enabled, press STEP and the system
displays:
Enter the 6-digit numeric passcode and press ENTER:
To enter the full volume of the tank (100% height) press CHANGE. Enter the volume in gallons or litres, depending
on the units established in System Setup (NOTE: Full Volume cannot be a volume less than the largest tank chart
volume). Press ENTER to confirm your entry. The system displays:
Press STEP to continue:
The Weights and Measures Officer presses CHANGE and enters the tank capacity. Press ENTER to accept the
value and press STEP to continue:
Press STEP to continue:
TANK PROFILE
ENTER PASSCODE->_______<
: 50 PTS
T1: (Product Label)
FULL VOL: 000000
FULL VOL: XXXXXX
PRESS <STEP> TO CONTINUE
T1: (Product Label)
TANK CAPACITY
: 000000
T1: (Product Label)
PROBE S/N
: XXXXXX
This display is view-only display and shows the serial number of the probe installed in the tank.
T1: VIEW HEIGHT/VOL PTS
PRESS <ENTER>
T1: ADD HEIGHT/VOL PTS
PRESS <ENTER>
T1: REMOVE HEIGHT/VOL PT
PRESS <ENTER>
Press STEP
Press STEP
See Paragraph D below
See Paragraph E below
See Paragraph F below