3.10.2 Tuning of control performance
Normally the default settings will result in good pressure control performance. For some applications tuning may be
required to improve performance.
The tuning procedures for each parameter (grey boxes) and its default values are described separately below. Strictly
keep the procedure order.
Required information for support:
•
Go to ‘Tools / Create Diagnostic File’ in ‘Control View’ resp. ‘Control Performance Analyzer’ and save file
•
Pressure / flow / gas conditions to be controlled
•
Chamber
volume
•
Pumping speed (l/s) and pump type (e.g. turbo pump)
•
System
description
•
Problem
description
Send diagnostic file with and all required information to
No
No
No
No
No
Gain factor
adjustment
Pressure
control
ok ?
Sensor delay
adjustment
Gain factor
adjustment
Setpoint ramp
adjustment
Valve speed
adjustment
Start
End
Pressure
control
ok ?
Pressure
control
ok ?
Pressure
control
ok ?
Contact
VAT
Pressure
control
ok ?
Reset gain
factor to 1.0
Set all
paramters to
default