Trouble shooting
Failure
Check
Action
No dots lighted on display
-
24 V power supply ok?
-
Connect valve to power supply according to
«Electrical connection» and make sure that power supply is
working.
Module Status LED is off
-
DeviceNet
®
power supply ok?
-
Connect valve to DeviceNet
®
according to
«DeviceNet connection» and make sure that power is
provided.
Module Status LED is flashing
green
-
The controller needs commissioning due to missing,
incomplete or incorrect configuration.
Module Status LED is flashing
red
(
recoverable fault
)
-
Refer to ODVA specification
volume II, release 2.0 (incl.
errata 1) «IDENTITY
OBJECT, figure 6.2, state
event matrix for identity
object»
-
Refer to ODVA specification volume II, release 2.0 (incl.
errata 1) «IDENTITY OBJECT, figure 6.2, state event
matrix for identity object»
Module Status LED is red
(
unrecoverable fault
)
-
Refer to ODVA specification
volume II, release 2.0 (incl.
errata 1) «IDENTITY
OBJECT, figure 6.2, state
event matrix for identity
object»
-
Refer to ODVA specification volume II, release 2.0 (incl.
errata 1) «IDENTITY OBJECT, figure 6.2, state event
matrix for identity object»
Network Status LED is off
(
Device is not on line
)
-
DeviceNet
®
power supply ok?
-
Connect valve to DeviceNet
®
according to
«DeviceNet connection» and make sure that power is
provided.
Network Status LED is flashing
green
(
on line but no connections in the
established state
)
-
Allocate device to master
Network Status LED is flashing
red
(
time out
)
-
Are I/O connections in the
time out state?
-
Reestablish I/O connections.
Network Status LED is red
-
Failed communication device. The device has detected an
error that has rendered it incapable of communicating on
the network.
Controller does not respond to
DeviceNet
®
commands
-
Node number and baudrate
correct?
-
Proceed according to «Setup procedure, DeviceNet
®
configuration ».
Controller does either not
respond or respond in an
unexpected way to DeviceNet
®
commands
-
Configuration correct?
-
Send FACTORY RESET and redo complete configuration.
Refer to «Explicit messaging control commands,
FACTORY RESET» and «Setup procedure, DeviceNet
®
configuration» for details.
Read back from controller is
wrong during polling
-
Check poll rate
-
Refer to «Setup procedure, DeviceNet
®
configuration» for
details.