3.6.4 ZERO
ZERO allows for the compensation of the sensor offset voltage.
When ZERO is performed the current value at the sensor input is equated to pressure zero. In case of a 2 sensor system
both sensor inputs will be adjusted. A max. offset voltage of +/- 1.4 V can be compensated. The offset value can be read
via local and remote operation.
Local operation
:
(„Control View‟, „Control Performance Analyzer‟ or
„Service Box 2„)
Remote operation
:
(Refer to chapter «Explicit messaging control
commands» resp. «Explicit messaging setup
commands» for details)
Go to
menu „Zero / ZERO‟ and follow instructions.
1. Send EXECUTING
(if not yet selected)
2. Select SETPOINT TYPE
= position control
3. Select CONTROL MODE for position
= open valve
4. Wait until process chamber is evacuated and
sensor signal is not shifting anymore.
5. Send ZERO
Note:
Do not perform ZERO as long as pressure gauge voltage is shifting otherwise incorrect pressure reading is the
result. Refer to manual of sensor manufacturer for warm up time.
Note:
Do not perform ZERO, if the base pressure of your vacuum system is higher than 1‰ of sensor full scale. We
recommend disabling ZERO function in this case; refer to «Valve and sensor configuration» of the setup procedure.
Otherwise incorrect pressure reading is the result.