3.11.2 Assembly object bit map
This is an example based on output assembly 8 and input assembly 3 to illustrate bit map.
DATA TYPE in this example is signed integer.
3.11.2.1 Output assembly
Assembly
Type
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
8
Output
1
MODE
2
SETPOINT low byte
3
SETPOINT high byte
4
SETPOINT TYPE
MODE
(control mode) may be set to one out of below selections, see also «Explicit messaging control commands»:
Description
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Control valve
0
0
0
0
0
0
0
0
Close valve
0
0
0
0
0
0
0
1
Open valve
0
0
0
0
0
0
1
0
Hold valve
0
0
0
0
0
0
1
1
SETPOINT
may be set to any value between the lowest and the highest value. Depending on SETPOINT TYPE it reflects
position or pressure setpoint , see also «Explicit messaging control commands».
Description
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Lowest value (0)
low byte
0
0
0
0
0
0
0
0
high byte
0
0
0
0
0
0
0
0
Highest value (10000)
low byte
0
0
0
1
0
0
0
0
high byte
0
0
1
0
0
1
1
1
SETPOINT TYPE
may be set to one out of below selections, see also «Explicit messaging control commands».
Description
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Pressure control
0
0
0
0
0
0
0
0
Position control
0
0
0
0
0
0
0
1