3.10.2.1 Gain factor adjustment
The gain factor effects:
Stability
Response time
Default value is 1. Adjustment range is from 0.0001 to 7.5.
Higher gain results in:
faster response
higher over- / undershoot of pressure
Lower gain results in:
slower response
lower over- / undershoot of pressure
Adjustment procedure:
1. Start with gain factor 1.0
2. Open valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with lower (higher) gain factors until optimal pressure response is achieved and stability is ok.
Note:
Normally adjustments down to gain factors of 0.42 should lead to good results. Otherwise you may need to
improve sensor connection. Refer to «Requirements to sensor connection».
Local operation
:
(„Control View‟, „Control Performance Analyzer‟ or
„Service Box 2„)
Remote operation
:
(Refer to chapter «Explicit messaging setup
commands» for details)
Set gain factor in menu „Setup / Control Parameter‟
Select PID CONTROLLER GAIN FACTOR