3.3 Cold load pick-up and inrush
current detection
3 Supporting functions
Technical description
112
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
Parameters of the cold load & inrush detection function
Parameter
Value
Unit
Description
Note
ColdLd
-
Start
Trip
Status of cold load detection:
Cold load situation is active
Timeout
Inrush
-
Start
Trip
Status of inrush detection:
Inrush is detected
Timeout
ILmax
A
The supervised value. Max. of
IL1, IL2 and IL3
Pickup
A
Primary scaled pick-up value
Idle
A
Primary scaled upper limit for
idle current
MaxTime
s
Set
Idle
xImode Current limit setting for idle
situation
Set
Pickup
xImode Pick-up setting for minimum
start current
Set
80
ms
Maximum transition time for
start recognition
Pickupf2
%
Pick-up value for relative
amount of 2
nd
harmonic, I
f2
/I
f1
Set
Set = An editable parameter (password needed)