2.2 Local panel operations
2 Local panel user interface
Operation and configuration
16
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
button is pressed within five minutes and there is no
VAMPSET communication, the force flag will be set to “Off”
position. The forcing is explained in Chapter 2.3.4.
Second menu of I>> 50/51 stage
Figure 0-2 Second menu(next on the right) of I>> 50/51 stage
This is the main setting menu. The content is:
Stage setting group 1
These are the group 1 setting values. The other setting
group can be seen by pressing push buttons ENTER and
then RIGHT or LEFT. Setting groups are explained in
chapter 2.2.3.
ILmax 403A
The maximum of three measured phase currents is at the
moment 403 A. This is the value the stage is supervising.
Status –
Status of the stage. This is just a copy of the status value in
the first menu.
I>> 1013 A
The pick-up limit is 1013 A in primary value.
I>> 2.50xIn
The pick-up limit is 2.50 times the rated current of the
generator. This value can be edited if the operating level is
at least “Operator”. Operating levels are explained in
chapter 2.2.5.
t>> 0.60s
The total operation delay is set to 600 ms. This value can be
edited if the operating level is at least “Operator”.
Содержание VAMP 59
Страница 2: ...2 VM59 EN001...
Страница 211: ...Technical description VM59 EN001 VAMP 24h support phone 358 0 20 753 3264 211...