5.8 Auto-reclose function (79)
5 Control functions
Technical description
156
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
Figure 5-5 Example sequence of two shots. After shot 2 the fault is cleared.
1.
Current exceeds the I> setting; the start delay from shot 1
starts.
2.
After the start delay, an OpenCB relay output closes.
3.
A CB opens. The dead time from shot 1 starts, and the
OpenCB relay output opens.
4.
The dead time from shot 1 runs out; a CloseCB output relay
closes.
5.
The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 1 starts. The current is still
over the I> setting.
6.
The discrimination time from the shot 1 runs out; the
OpenCB relay output closes.
7.
The CB opens. The dead time from shot 2 starts, and the
OpenCB relay output opens.
8.
The dead time from shot 2 runs out; the CloseCB output
relay closes.
9.
The CB closes. The CloseCB output relay opens, and the
discrimination time from shot 2 starts. The current is now
under I> setting.
10.
Reclaim time starts. After the reclaim time the AR sequence
is successfully executed. The AR function moves to wait for
a new AR request in shot 1.