2.3 Operating measures
2 Local panel user interface
Operation and configuration
22
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
2.3.
Operating measures
2.3.1.
Control functions
The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-
reclose on/off selection and selected analogue measurement
values.
Please note that the operator password must be active in order
to be able to control the objects. Please refer to page 21 opening
access.
Toggling Local/Remote control
1.
Push the ENTER key. The previously activated object starts
to blink.
2.
Select the Local/Remote object (“L” or “R” squared) by using
the arrow keys.
3.
Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local
control. Select “LOCAL” to enable local control and disable
remote control.
4.
Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
Object control
Using ENTER and UP / DOWN keys
1.
Push the ENTER key. The previously activated object starts
to blink.
2.
Select the object to control by using the arrow keys. Please
note that only controllable objects can be selected.
3.
Push the ENTER key. A control dialog opens.
4.
Select the “Open” or “Close” command by using the UP and
DOWN arrow keys.
5.
Confirm the operation by pushing the ENTER key. The
state of the object changes.