5.7 Controllable objects
5 Control functions
Technical description
148
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
Output signals of controllable objects
Each controllable object has 2 control signals in matrix:
Output signal
Description
Object x Open
Open control signal for the object
Object x Close
Close control signal for the object
These signals send control pulse when an object is controlled by
digital input, remote bus, auto-reclose etc.
Settings for read-only objects
Each read-only object has the following settings:
Setting
Value
Description
DI for „obj open‟
None, any digital
input, virtual input
or virtual output
Open information
DI for „obj close‟
Close information
Object timeout
0.02 … 600 s
Timeout for state
changes
If changing states takes longer than the time defined by “Object
timeout” setting, object fails and “Object failure” matrix signal
is set. Also undefined-event is generated.
Controlling with DI
Objects can be controlled with digital input, virtual input or
virtual output. There are four settings for each controllable
object:
Setting
Active
DI for remote open control
In remote state
DI for remote close control
DI for local open control
In local state
DI for local close control
If the device is in local control state, the remote control inputs
are ignored and vice versa. Object is controlled when a rising
edge is detected from the selected input. Length of digital input
pulse should be at least 60 ms.
Controlling with F1 & F2
Objects can be controlled with F1 & F2. There are two settings
for each controllable object:
Setting
Active
DI for local open control
In local state
DI for local close control
Selected object and control is shown in VAMPSET software
under the menu ”FUNCTION BUTTONS”. If no object with
local control is selected ‟-‟ is shown. If multiple local controls
are selected for one key ‟?‟ is shown.