Technical description
2 Protection functions
2.14 Inverse time operation
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
95
t
= Operation delay in seconds
k
= User‟s multiplier
I
= Measured value
I
PICKUP
= User‟s pick up setting
A,B,C = Constant parameter according Table 2.14.1-3.
Table 2.14.1-3 Constants for IEEE/ANSI inverse delay equation
Delay type
Parameter
A
B
C
LTI
Long time inverse
0.086
0.185
0.02
LTVI
Long time very inverse
28.55
0.712
2
LTEI
Long time extremely
inverse
64.07
0.250
2
MI
Moderately inverse
0.0515
0.1140
0.02
VI
Very inverse
19.61
0.491
2
EI
Extremely inverse
28.2
0.1217
2
STI
Short time inverse
0.16758
0.11858
0.02
STEI
Short time extremely
inverse
1.281
0.005
2
Example for Delay type "Moderately inverse (MI)":
k
= 0.50
I
= 4 pu
I
PICKUP
= 2 pu
A
= 0.0515
B
= 0.114
C
= 0.02
9
.
1
1140
.
0
1
2
4
0515
.
0
50
.
0
02
.
0
t
The operation time in this example will be 1.9 seconds. The
same result can be read from Figure 2.14.1-8.