6.2 Communication protocols
6 Communication
Technical description
164
VAMP 24h support phone +358 (0)20 753 3264
VM59.EN001
IEC 61850 main config parameters
Parameter Value
Unit Description
Set
Port
0 - 64000
IP protocol port
Set
Check
upper
addresses
Yes / No
If the checkbox 'Check
upper addresses' is
checked the below
parameters are also
checked and used for
addressing when the
client is communicating
to the device, by default
this is disabled.
Set
.
The below parameters
are ACSE association
parameters described in
the standard part 61850-
8-1
AP ID
nnn.nnn.nnn.nnn
ACSE AP title value
Set
AE
Qualifier
0 – 64000
ACSE AE qualifier
P Selector
0 – 4200000000
Presentation selector
S Selector
0 – 64000
Session selector
T Selector
0 – 64000
Transport selector
IED Name
String
Identifcation of the
device. Each device must
have unique name.
Delete
dynamic
datasets
command
Send command to clear
all dynamic datasets