Technical description
3 Supporting functions
3.10 Self-supervision
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
129
3.10.
Self-supervision
The functions of the microcontroller and the associated
circuitry, as well as the program execution are supervised by
means of a separate watchdog circuit. Besides supervising the
relay, the watchdog circuit attempts to restart the micro
controller in a fault situation. If the restarting fails, the
watchdog issues a self-supervision alarm indicating a
permanent internal fault.
When the watchdog circuit detects a permanent fault, it always
blocks any control of other output relays (except for the self-
supervision output relay).
In addition, the internal supply voltages are supervised. Should
the auxiliary supply of the relay disappear, an alarm is
automatically given because the internal fault (IF) output relay
functions on a working current principle. This means that the
IF relay is energized when the auxiliary supply is on and no
internal fault is detected.
3.10.1.
Diagnostics
The device runs self-diagnostic tests for hardware and software
in every boot sequence and also performs runtime checking.
Fatal errors
If fatal error has been detected, the device releases IF relay
contact and error led is set on. Local panel will also display an
error message about the detected fault. Fatal error state is
entered when the device is not able to handle protections.
Runtime errors
When self-diagnostic function detects a fault, Selfdiag Alarm
matrix signal is set and an event (E56) is generated. In case the
error was only temporary, an off event is generated (E57). Self
diagnostic error can be reset via local panel interface.